ENG
The converter takes 12 V from the panel or an external supply and provides 24 V for special detectors. Mounted inside the panel (installation kit 788605) it supplies up to four special detectors with 125 mA each or one with 500 mA; each output is separately fused.
| Operating voltage | 9 … 15 V DC |
|---|---|
| Output voltage | 24 V DC ± 10 % |
| Output current | max. 500 mA (4 x 125 mA) |
| Protection rating | IP 40 (housing) |
| Operating temperature | -10 °C … 50 °C |
| Storage temperature | -15 °C … 55 °C |
| Humidity | < 95 % (non-condensing) |
| Dimensions | 65 × 72 × 20 mm (W × H × D) |
| Weight | approx. 150 g |