| IP kaitseaste | IP43 |
|---|
The ATEX-approved optical smoke detector detects fires early and responds well to smouldering fires. It connects directly to the esserbus loop via Ex barrier 804744 and is fully addressable without using a loop address for a transponder. Base ordered separately.
| Operating voltage | 8 … 42 V DC |
|---|---|
| Quiescent current | approx. 50 µA |
| Alarm current | typ. 18 mA |
| Monitored area | max. 110 m² |
| Mounting height | max. 12 m |
| Air velocity | 0 … 25.4 m/s |
| Standard | EN 54-7 : 2006 |
| Explosion protection | Ex ib IIC T4 Gb |
| EC-type examination certificate | TÜV 09 ATEX 554910 |
| Protection rating | IP 43 (incl. base + option) |
| Operating temperature | -20 °C … 70 °C |
| Storage temperature | -25 °C … 75 °C |
| Humidity | < 95 % (non-condensing) |
| Material | ABS |
| Colour | white, similar to RAL 9010 |
| Dimensions | Ø 117 mm, height 49 mm (62 mm incl. base) |
| Weight | approx. 110 g |