ENG
| IP kaitseaste | IP43 |
|---|
In addition to smoke and heat detection with O²T multisensor technology, the detector has a built-in sounder whose volume can be set to eight levels. The sounder is loop-powered and needs no additional address.
| Operating voltage | 8 … 42 V DC |
|---|---|
| Quiescent current | approx. 80 µA |
| Monitored area | max. 110 m² |
| Mounting height | max. 12 m |
| Air velocity | 0 … 25.4 m/s |
| Standard | EN 54-7/-5 B/-17, CEA 4021 |
| Protection rating | IP43 (with base + options) |
| Operating temperature | -20 °C … 65 °C |
| Storage temperature | -25 °C … 75 °C |
| Humidity | < 95 % (non-condensing) |
| Material | ABS plastic |
| Colour | white, similar to RAL 9010 |
| Dimensions | Ø 117 mm, height 67 mm (incl. base) |
| Weight | approx. 145 g |