ENG
| Manufacturer | Honeywell |
|---|---|
| Length | 265 |
| Width | 483 |
| Height | 218 |
Morley MAx MA-2000 is a two-loop multiprocessor fire detection panel for hotels, offices, hospitals and industrial buildings. The 7" TFT touch screen and the dedicated keys below it make daily operation simple; panels are networked over two opto-isolated CAN bus lines into a fail-safe closed-loop network of up to 64 panels or 128 loops. The panel can be wall mounted, flush mounted with the MA-2BZL bezel or installed in a 19" rack (6U).
| Loops | 2 |
|---|---|
| Devices per loop | 99 detectors + 99 modules |
| Display | 7" TFT touch screen, 800 × 480 |
| Network | CAN bus, up to 64 panels / 128 loops |
| Mains supply | 100–240 V AC, 50/60 Hz, max. 1.7 A @ 230 V AC |
| Batteries | 2 × 12 V, max. 17 Ah |
| Loop current | 750 mA |
| Outputs | 1 fault (NO/NC); 1 alarm + 2 programmable (NO/NC or monitored 1 A) |
| Sounder output | 1, monitored, 1 A |
| 24 V DC output | max. 1 A |
| Interfaces | USB, RS485 (repeaters), RS232/RS485 |
| Standards | EN 54-2, EN 54-4, EN 54-13 |
| Protection rating | IP30 |
| Colour | RAL 9002 |
| Dimensions | 483 × 265 × 217.5 mm (W × H × D), 6U |
| Weight | 6 kg |
| Operating temperature | −5 … +40 °C |
| Storage temperature | −10 … +50 °C |
| Humidity | 5–95 %, non-condensing |