ENG
| Manufacturer | Honeywell |
|---|
MI-CR6-S2I has six Form C (changeover) relays, each on its own address. The first address is set with rotary switches from 01 to 94 and the next five are assigned automatically; up to three unused addresses can be disabled. Each address provides one isolated set of volt-free contacts that can be wired normally open or normally closed, and the panel switches the contacts on demand. The controlled circuit is not supervised. Each relay has its own LED.
| Inputs/outputs | 6 changeover relays (Form C) |
|---|---|
| Relay rating | 3 A @ 30 V DC (resistive) |
| Addresses | 6 addresses, first 01–94 |
| Operating voltage | 15–32 V DC |
| Standby current | 1.49 mA (LED blinking every 5 s) |
| Alarm current | 36 mA @ 32 V (all relays and LEDs on) |
| Terminals | 1.0–2.0 mm² |
| Dimensions | 173 × 147 × 32 mm (H × W × D) |
| Operating temperature | 0 … +50 °C |
| Humidity | 10–90 %, non-condensing |