ENG
| Manufacturer | Honeywell |
|---|---|
| Length | 102 |
| Height | 61 |
HM-RHSE-I-AP is an analogue addressable rate-of-rise heat detector from the Morley HM series. Its thermistor and microprocessor raise an alarm when the temperature rises faster than typically 10 °C per minute or exceeds 58 °C (class A1R). Two red LEDs show the status from every direction, and the built-in isolator cuts off only the faulty loop section in case of a short circuit. The detector uses the Advanced Protocol and fits the MI/B501AP/IV base. Not for locations where the normal ambient temperature exceeds 50 °C.
| Type | rate-of-rise heat detector, 58 °C + ~10 °C/min |
|---|---|
| Standards | EN 54-5 A1R, EN 54-17 |
| Operating voltage | 15–28 V DC |
| Standby current | 160 µA @ 24 V DC (300 µA with LED blink) |
| LED current | 3.5 mA @ 24 V DC |
| Remote indicator output | 22.5 V DC / 10.8 mA @ 24 V DC |
| Terminals | up to 2.5 mm² |
| Colour | ivory |
| Material | PC/ABS |
| Dimensions | Ø 102 mm, height 61 mm (with base) |
| Weight | 88 g (with base) |
| Operating temperature | −30 … +70 °C |
| Humidity | 10–93 %, non-condensing |