ENG
The UIM (Universal Interface Module) connects two analogue audio inputs, two outputs and 48 programmable control contacts to the Variodyn ONE system; eight contacts can be monitored for short circuit and interruption. It connects to the INC via the DAL bus, digitises audio e.g. from a CD player or a fire alarm panel and sends it to the INC.
| Power consumption | < 150 mA @ 24 V DC |
|---|---|
| Operating temperature | -5 °C … +55 °C |
| Storage temperature | -10 °C … +60 °C |
| Humidity | 15 % … 90 % rel. hum. (non-condensing) |
| Colour | Grey, similar to RAL 7016 approx. |
| Dimensions | (W x H x D) 483 x 44 x 345 mm (1 HU) |
| Weight | Approx. 7.22 kg |